What is the difference between 100a rated rv pedestal and 200amp pedestals? Is it how many pedestals you can loop through? Say 100amp rated rv pedestals could have 1 100 amp circuit feeding 2 rv pedestal sites using the loop through lugs @ each pedestal But a 200 amp rated rv pedestal could have 1 200 amp circuit feeding 4 sites (possibly 6) using the loop through lugs @ each pedestal ?
1st ISSUE Is a grounding electrode required for an RV pedestal that has a 50 amp breaker and receptacle with a 20 amp receptacle and breaker? If my understanding is correct it is not required based on 2020 250.50 as the GE is required for each building or structure and in definitions the...
Does each pedestal have an individual run to the transformer or did they daisy chain conductors between pedestals? Individual run to each pedestal would comply with 230.2 and 230.40 Daisy chaining them would need to be arranged so that the first one contains the service disconnecting means and the rest would be feeder supplied.
The thought process is that only (1) boat per slip could use the pedestal but (1) boat could use (2) 50A receptacles at the same time. Now, lets say there were (6) of these pedestals.